OU Sarkeys Energy Center Energy Recovery Wheels |
|
Replace (6) 30,000 CFM Total Energy Recover Wheels
Location: Norman, Oklahoma
Owner: The University of Oklahoma
Mechanical Contractor: Matherly Mechanical Contractors Inc.
Project Data:
This project consisted of removing (6) 12’-0” x 12’-0” x 2’-0” Energy Recovery Wheels that were originally installed in the early 1980s and install (6) new Semco Total Energy Recovery Wheels with 3 Å Molecular Sieve Desiccant Coating and new DDC control system. These wheels had to be changed out without shutting down the building air handling systems for a prolong time period. This was achieved by isolating each wheel section, and steam pre- heat coil with a custom designed blank off panel system.
Energy Wheel Data Per Wheel:
Cooling Season * Outdoor Air 32,860 CFM * Supply Air 30,000 CFM 100˚db / 74˚wb 73.8˚db / 67˚wb 91 gr 93.5 gr 37.0 BTU / lb 32.5 BTU / lb
* Exhaust Air 32,860 CFM * Return Air 30,000 CFM 93.2˚db / 74˚wb 67.0˚db / 65˚wb 91.7 gr 94.1 gr 37.0 BTU / lb 30.9BTU / lb
Heating * Outdoor Air 32,860 CFM * Supply Air 30,000 CFM 0.0˚db / -2.0˚wb 53.1˚db / 42.3˚wb 1.5 gr 24.6 gr 0.1BTU / lb 16.6 BTU / lb